1 | 0 | Reserved | Reserved | |||||||
---|---|---|---|---|---|---|---|---|---|---|
2 | 1 | HREG_T_OP1 | int16 | 10 | Room temperature sensor TE20 | Temperature at operator panel 1 | Temperature at operator panel 1 | |||
3 | 2 | HREG_T_OP2 | int16 | 10 | Room temperature sensor TE21 | Temperature at operator panel 2 | Temperature at operator panel 2 | |||
4 | 3 | HREG_EFFECTIVE_TF | uint16 | 1 | Current supply fan speed | The current effective TF fanspeed | Fan speed, supply air | Current supply air fan speed | ||
5 | 4 | HREG_EFFECTIVE_PF | uint16 | 1 | Current exhaust fan speed | The current effective PF fanspeed | Fan speed, extract air | Current extract air fan speed | ||
6 | 5 | HREG_UPCOMING_TIME_PROGRAM | uint16 | 1 | Next time program | Indicates the time program which will start during the next two hours. | Values 1-20 indicate week program slots, value 101-105 indicate year program slots | |||
7 | 6 | HREG_T_FRS | int16 | 10 | Fresh air | TE01 (fresh air) temperature. | Fresh air | Outside air temperature at the unit (sensor TE01) | ||
8 | 7 | HREG_T_SPLY_LTO | int16 | 10 | Supply air after HRC | TE05: Fresh (incoming) air temperature after HRC. | Supply air after HRC | Supply air temperature after heat recovery (sensor TE05) | ||
9 | 8 | HREG_T_SPLY | int16 | 10 | Supply air | TE10 Room supply air temperature | Supply air | Supply air temperature after supply air heater (sensor TE10) | ||
10 | 9 | HREG_T_WST | int16 | 10 | Waste air | TE32 Waste air temperature | Exhaust air | Exhaust air temperature (sensor TE32) | ||
11 | 10 | HREG_T_EXT | int16 | 10 | Room removed air | TE30 Room removed air temperature. | Extract air temperature | Extract air temperature from building at the unit (sensor TE30) | ||
12 | 11 | HREG_T_EXT_LTO | int16 | 10 | Removed air before HRC | TE31 removed air before heat recycler. | Extract air before HRC | Extract air temperature after extract air coil before heat recovery in HP units (sensor TE31) | ||
13 | 12 | HREG_T_WR | int16 | 10 | Return water | TE45 heater element return water temperature. | Return water | Return water temperature in supply air heater (sensor TE45) | ||
14 | 13 | HREG_HUM_EXT | uint16 | 1 | Exhaust air humidity | RH30 measurement, removed air relative humidity | Air humidity | Extract air relative humidity \%RH at the unit (sensor RH30) | ||
15 | 14 | HREG_PRES_SPLYF | uint16 | 1 | Pressure difference supply | Pressure difference over filter, TF side | Pressure difference supply | Pressure difference over filter, TF side | ||
16 | 15 | HREG_PRES_EXTF | uint16 | 1 | Pressure difference ext | Pressure difference over filter, PF side | Pressure difference ext. | Pressure difference over filter, PF side | ||
17 | 16 | HREG_TE07 | int16 | 10 | HP/MDX/Dehum supply air | Supply air temperature after dehumidification coil, or after heat pump coil in HP-E, HP-W, MDX-E and MDX-W units (sensor TE07) | ||||
18 | 17 | HREG_AI1 | uint16 | 10 | Analog input voltage | Raw conversion result for AI1 | Measured input voltage AI1 | Current measured input voltage | ||
19 | 18 | HREG_AI2 | uint16 | 10 | Analog input voltage | Raw conversion result for AI2 | Measured input voltage AI2 | Current measured input voltage | ||
20 | 19 | HREG_AI3 | uint16 | 10 | Analog input voltage | Raw conversion result for AI3 | Measured input voltage AI3 | Current measured input voltage | ||
21 | 20 | HREG_AI4 | uint16 | 10 | Analog input voltage | Raw conversion result for AI4 | Measured input voltage AI4 | Current measured input voltage | ||
22 | 21 | HREG_AI5 | uint16 | 10 | Analog input voltage | Raw conversion result for AI5 | Measured input voltage AI5 | Current measured input voltage | ||
23 | 22 | HREG_AI6 | uint16 | 10 | Analog input voltage | Raw conversion result for AI6 | Measured input voltage AI6 | Current measured input voltage | ||
24 | 23 | HREG_AI1_RES | uint16 | 1 | Calculated value | Calculated result for AI1 | Calculated value AI1 | Calculated result | ||
25 | 24 | HREG_AI2_RES | uint16 | 1 | Calculated value | Calculated result for AI2 | Calculated value AI2 | Calculated result | ||
26 | 25 | HREG_AI3_RES | uint16 | 1 | Calculated value | Calculated result for AI3 | Calculated value AI3 | Calculated result | ||
27 | 26 | HREG_AI4_RES | uint16 | 1 | Calculated value | Calculated result for AI4 | Calculated value AI4 | Calculated result | ||
28 | 27 | HREG_AI5_RES | uint16 | 1 | Calculated value | Calculated result for AI5 | Calculated value AI5 | Calculated result | ||
29 | 28 | HREG_AI6_RES | uint16 | 1 | Calculated value | Calculated result for AI6 | Calculated value AI6 | Calculated result | ||
30 | 29 | HREG_LTO_N_SPLY | uint16 | 1 | Heat recovery efficiency n supply | HRC efficiency ratio (supply side) | Heat recovery efficiency, supply air | Supply air temperature efficiency. Calculated from outside air-, supply air after heat recovery- and extract air temperature | ||
31 | 30 | HREG_LTO_N_EXT | uint16 | 1 | Heat recovery efficiency n exhaust | HRC efficiency ratio (ext (removed air) side) | Heat recovery efficiency, exhaust air | Extract air temperature efficiency. Calculated from extract air-, exhaust air- and outside air temperature. In HP-units calculated from HRC extract air-, exhaust air- and outside air temperature | ||
32 | 31 | HREG_NTC_X6 | int16 | 10 | Input X6 | Optional NTC-10 input X6 measurement | ||||
33 | 32 | HREG_NTC_X7 | int16 | 10 | Input X7 | Optional NTC-10 input X7 measurement | ||||
34 | 33 | HREG_ABS_HUM_CTRL_OUTPUT | int16 | 1 | Absolute humidity control output | -100...0% = dehumidifying, 0 = none, 0...100% = humidifying | ||||
35 | 34 | HREG_NWK_STATUS | bitfield | 1 | Network status | Ethernet block status | EMAC_STATUS_FAIL 0x0001, EMAC_STATUS_OK 0x0002, EMAC_STATUS_AUTONEG_COMPLETE 0x0004, EMAC_STATUS_AUTONEG_FAIL 0x0008, EMAC_STATUS_LINK_OK 0x0010 /* 0: no link, 1: link ok */, EMAC_STATUS_LINK_SPEED 0x0020 /* 0: 10 M, 1: 100M */, EMAC_STATUS_DUPLEX 0x0040 /* 0: half duplex, 1: full duplex */ , EMAC_STATUS_INIT_ONGOING 0x0080 | |||
36 | 35 | HREG_RH_MEAN | uint16 | 1 | 48h air humidity average | Mean relative humidity, with 48 hour history, updated every hour. | Average air humidity, 48h | Extract air 48h mean relative humidity \%RH at the unit (sensor RH30). Updated every hour | ||
37 | 36 | HREG_ABSHUM10 | uint16 | 10 | Supply air absolute humidity | Supply air absolute humidity, calculated from sensors TE10 and RH10, assuming normal atmospheric pressure. | ||||
38 | 37 | HREG_SEC_RTC | uint16 | 1 | s | RTC seconds. | s | RTC seconds | ||
39 | 38 | HREG_MIN_RTC | uint16 | 1 | min | RTC minutes. | min | RTC minutes | ||
40 | 39 | HREG_HOUR_RTC | uint16 | 1 | h | RTC hours, 24 hour format. | h | RTC hours, 24 hour format | ||
41 | 40 | HREG_DAY_RTC | uint16 | 1 | RTC day-of-month | RTC day of month | ||||
42 | 41 | HREG_MONTH_RTC | uint16 | 1 | RTC month. | RTC month | ||||
43 | 42 | HREG_YEAR_RTC | uint16 | 1 | RTC year, exporessed in years since 2000. | RTC year, expressed in years since 2000 | ||||
44 | 43 | Reserved | Reserved | |||||||
45 | 44 | HREG_MODE | bitfield | 1 | Status | The current mode of the machine, used to display information to the user. | Status | All current states of unit, eg. Home, Central vacuum cleaner, HP/EDX defrost etc. | Bit 0 indicates Max cooling mode, bit 1: max heating. Bit 2: Machine is stopped due to A alarm. Bit 3 indicates the machine has been stopped by request (ie. not due to alarm condition). Bit 4: indicates Away state. Bit 5 is reserved. Bit 6 indicates temperature boosting, bit 7 CO2 boosting, bit 8 RH boosting, bit 9 manual boosting. Bit 10 overpressure mode, bit 11 cooker hood mode, bit 12 central vacuum cleaner mode. Bit 13 indicates cool-off period of electrical heating coil. Bit 14 indicates summer night cooling mode. Bit 15 indicates heat recovery wheel defrosting mode. Value 0 indicates <20>normal<61> state, no special status is active. | |
46 | 45 | HREG_EXTMODE | bitfield | 1 | Temperature control step | Currently active temperature control step: Cooling, Heat recovery (LTO), or heating. | Temperature controller | Displays current state of temperature controller; cooling, heat recovery, heating or none. | Bits 0,1,2,3 have <20>enumerated<65> meaning: TEMP_STEP_NONE = 0, TEMP_STEP_COOLING = 1, TEMP_STEP_LTO = 2, TEMP_STEP_HEATING = 4, TEMP_STEP_STARTUP = 7, TEMP_STEP_DEHUMIDIFICATION = 8. Bit 15 indicates Aqua mode, bit 14 indicates pre-heating active, bit 13 indicates that HP compressor effect is being limited, bit 12 indicates defrosting state of the HP or MDX unit | |
47 | 46 | HREG_ROOM_TEMP | int16 | 10 | Room temperature average | TE20 room temperature, average value calculated from op panel sensors and room temperature transmitters. | Room temperature average | Room temperature (average temperature of sensors connected to OP wallmounts and AI temperature measurements if connected) | ||
48 | 47 | HREG_CASCADE_SP | int16 | 10 | Setpoint for supply air | Setpoint for temperature controller responsible for maintaining the room supply air at a constant level | Setpoint for supply air | Setpoint for temperature controller responsible for maintaining the room supply air at a constant level | ||
49 | 48 | HREG_DISPLAY_SP | int16 | 10 | Temperature controller setpoint shown to user | |||||
50 | 49 | HREG_OUTPUT | int16 | 1 | Controller output | Output from the TC1 temperature PI controller | Temperature controller output | -200 to -100 additional cooling, -100...-1=cooling, 0=nothing, 1...100=heat recovery, 101...200=additional heating or heat pump, 201...300=additional heating in heat pump units | ||
51 | 50 | Reserved | Reserved | |||||||
52 | 51 | Reserved | Reserved | |||||||
53 | 52 | Reserved | Reserved | |||||||
54 | 53 | Reserved | Reserved | |||||||
55 | 54 | Reserved | Reserved | |||||||
56 | 55 | Reserved | Reserved | |||||||
57 | 56 | Reserved | Reserved | |||||||
58 | 57 | Reserved | Reserved | |||||||
59 | 58 | Reserved | Reserved | |||||||
60 | 59 | Reserved | Reserved | |||||||
61 | 60 | Reserved | Reserved | |||||||
62 | 61 | Reserved | Reserved | |||||||
63 | 62 | Reserved | Reserved | |||||||
64 | 63 | Reserved | Reserved | |||||||
65 | 64 | Reserved | Reserved | |||||||
66 | 65 | Reserved | Reserved | |||||||
67 | 66 | Reserved | Reserved | |||||||
68 | 67 | Reserved | Reserved | |||||||
69 | 68 | Reserved | Reserved | |||||||
70 | 69 | Reserved | Reserved | |||||||
71 | 70 | Reserved | Reserved | |||||||
72 | 71 | Reserved | Reserved | |||||||
73 | 72 | Reserved | Reserved | |||||||
74 | 73 | Reserved | Reserved | |||||||
75 | 74 | Reserved | Reserved | |||||||
76 | 75 | Reserved | Reserved | |||||||
77 | 76 | Reserved | Reserved | |||||||
78 | 77 | Reserved | Reserved | |||||||
79 | 78 | Reserved | Reserved | |||||||
80 | 79 | Reserved | Reserved | |||||||
81 | 80 | Reserved | Reserved | |||||||
82 | 81 | Reserved | Reserved | |||||||
83 | 82 | Reserved | Reserved | |||||||
84 | 83 | Reserved | Reserved | |||||||
85 | 84 | Reserved | Reserved | |||||||
86 | 85 | Reserved | Reserved | |||||||
87 | 86 | Reserved | Reserved | |||||||
88 | 87 | Reserved | Reserved | |||||||
89 | 88 | Reserved | Reserved | |||||||
90 | 89 | Reserved | Reserved | |||||||
91 | 90 | Reserved | Reserved | |||||||
92 | 91 | Reserved | Reserved | |||||||
93 | 92 | Reserved | Reserved | |||||||
94 | 93 | Reserved | Reserved | |||||||
95 | 94 | Reserved | Reserved | |||||||
96 | 95 | Reserved | Reserved | |||||||
97 | 96 | Reserved | Reserved | |||||||
98 | 97 | Reserved | Reserved | |||||||
99 | 98 | Reserved | Reserved | |||||||
100 | 99 | Reserved | Reserved | |||||||
101 | 100 | Reserved | Reserved | |||||||
102 | 101 | Reserved | Reserved | |||||||
103 | 102 | Reserved | Reserved | |||||||
104 | 103 | Reserved | Reserved | |||||||
105 | 104 | HREG_AI1_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI1. | Sensor type | |||
106 | 105 | HREG_AI2_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI2. | Sensor type | |||
107 | 106 | HREG_AI3_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI3. | Sensor type | |||
108 | 107 | HREG_AI4_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI4. | Sensor type | |||
109 | 108 | HREG_AI5_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI5. | Sensor type | |||
110 | 109 | HREG_AI6_TYPE | uint16 | 1 | Sensor type | Type of external sensor in AI6. | Sensor type | |||
111 | 110 | HREG_AI1_VL | uint16 | 10 | 0 - 100 | Voltage low | AI1 voltage low | Voltage low | Input signal lower limit | |
112 | 111 | HREG_AI2_VL | uint16 | 10 | 0 - 100 | Voltage low | AI2 voltage low | Voltage low | Input signal lower limit | |
113 | 112 | HREG_AI3_VL | uint16 | 10 | 0 - 100 | Voltage low | AI3 voltage low | Voltage low | Input signal lower limit | |
114 | 113 | HREG_AI4_VL | uint16 | 10 | 0 - 100 | Voltage low | AI4 voltage low | Voltage low | Input signal lower limit | |
115 | 114 | HREG_AI5_VL | uint16 | 10 | 0 - 100 | Voltage low | AI5 voltage low | Voltage low | Input signal lower limit | |
116 | 115 | HREG_AI6_VL | uint16 | 10 | 0 - 100 | Voltage low | AI6 voltage low | Voltage low | Input signal lower limit | |
117 | 116 | HREG_AI1_VH | uint16 | 10 | 0 - 100 | Voltage high | AI1 voltage high | Voltage high | Input signal upper limit | |
118 | 117 | HREG_AI2_VH | uint16 | 10 | 0 - 100 | Voltage high | AI2 voltage high | Voltage high | Input signal upper limit | |
119 | 118 | HREG_AI3_VH | uint16 | 10 | 0 - 100 | Voltage high | AI3 voltage high | Voltage high | Input signal upper limit | |
120 | 119 | HREG_AI4_VH | uint16 | 10 | 0 - 100 | Voltage high | AI4 voltage high | Voltage high | Input signal upper limit | |
121 | 120 | HREG_AI5_VH | uint16 | 10 | 0 - 100 | Voltage high | AI5 voltage high | Voltage high | Input signal upper limit | |
122 | 121 | HREG_AI6_VH | uint16 | 10 | 0 - 100 | Voltage high | AI6 voltage high | Voltage high | Input signal upper limit | |
123 | 122 | HREG_AI1_RL | int16 | 1 | Result low | AI1 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
124 | 123 | HREG_AI2_RL | int16 | 1 | Result low | AI2 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
125 | 124 | HREG_AI3_RL | int16 | 1 | Result low | AI3 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
126 | 125 | HREG_AI4_RL | int16 | 1 | Result low | AI4 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
127 | 126 | HREG_AI5_RL | int16 | 1 | Result low | AI5 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
128 | 127 | HREG_AI6_RL | int16 | 1 | Result low | AI6 output value from voltage low | Voltage low, effect | Result of input signal equivalent to Voltage low value | ||
129 | 128 | HREG_AI1_RH | int16 | 1 | Result high | AI1 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
130 | 129 | HREG_AI2_RH | int16 | 1 | Result high | AI2 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
131 | 130 | HREG_AI3_RH | int16 | 1 | Result high | AI3 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
132 | 131 | HREG_AI4_RH | int16 | 1 | Result high | AI4 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
133 | 132 | HREG_AI5_RH | int16 | 1 | Result high | AI5 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
134 | 133 | HREG_AI6_RH | int16 | 1 | Result high | AI6 output value from voltage high | Voltage high, effect | Result of input signal equivalent to Voltage high value | ||
135 | 134 | HREG_TE01_24H_AVG | int16 | 10 | Average outside temperature | 24-hour outside temperature average | ||||
136 | 135 | HREG_T_SETPOINT | int16 | 10 | 0 - 500 | Supply air setpoint | The desired setpoint set by the user. | Supply air setpoint | Desired setpoint set by the user | |
137 | 136 | Reserved | Reserved | |||||||
138 | 137 | HREG_TE01_SUMMER_WINTER_THRESHOLD | int16 | 10 | -250 | Summer/Winter threshold | Summer/Winter season 24-hour average outside temperature threshold value | Summer/winter threshold temperature | Outside air 24h average temperature; in summer mode extract air 48h average humidity, in winter mode a fixed \%RH threshold | |
139 | 138 | Reserved | Reserved | |||||||
140 | 139 | Reserved | Reserved | |||||||
141 | 140 | Reserved | Reserved | |||||||
142 | 141 | Reserved | Reserved | |||||||
143 | 142 | Reserved | Reserved | |||||||
144 | 143 | Reserved | Reserved | |||||||
145 | 144 | Reserved | Reserved | |||||||
146 | 145 | Reserved | Reserved | |||||||
147 | 146 | Reserved | Reserved | |||||||
148 | 147 | Reserved | Reserved | |||||||
149 | 148 | Reserved | Reserved | |||||||
150 | 149 | Reserved | Reserved | |||||||
151 | 150 | Reserved | Reserved | |||||||
152 | 151 | Reserved | Reserved | |||||||
153 | 152 | Reserved | Reserved | |||||||
154 | 153 | Reserved | Reserved | |||||||
155 | 154 | Reserved | Reserved | |||||||
156 | 155 | Reserved | Reserved | |||||||
157 | 156 | Reserved | Reserved | |||||||
158 | 157 | Reserved | Reserved | |||||||
159 | 158 | Reserved | Reserved | |||||||
160 | 159 | Reserved | Reserved | |||||||
161 | 160 | Reserved | Reserved | |||||||
162 | 161 | Reserved | Reserved | |||||||
163 | 162 | Reserved | Reserved | |||||||
164 | 163 | Reserved | Reserved | |||||||
165 | 164 | Reserved | Reserved | |||||||
166 | 165 | Reserved | Reserved | |||||||
167 | 166 | Reserved | Reserved | |||||||
168 | 167 | Reserved | Reserved | |||||||
169 | 168 | Reserved | Reserved | |||||||
170 | 169 | Reserved | Reserved | |||||||
171 | 170 | Reserved | Reserved | |||||||
172 | 171 | Reserved | Reserved | |||||||
173 | 172 | HREG_TEMP_DECREASE_VAL | int16 | 10 | 0 - 150 | Temperature decrease | The amount of degrees the temperature should be lowered then temperature decrease function is on. | Temperature decrease | Number of degrees, under which the temperature should be maintained when temperature decrease function is on | Low limit can be negative to enable temperature increase function. |
174 | 173 | Reserved | Reserved | |||||||
175 | 174 | Reserved | Reserved | |||||||
176 | 175 | Reserved | Reserved | |||||||
177 | 176 | Reserved | Reserved | |||||||
178 | 177 | Reserved | Reserved | |||||||
179 | 178 | Reserved | Reserved | |||||||
180 | 179 | Reserved | Reserved | |||||||
181 | 180 | Reserved | Reserved | |||||||
182 | 181 | Reserved | Reserved | |||||||
183 | 182 | Reserved | Reserved | |||||||
184 | 183 | Reserved | Reserved | |||||||
185 | 184 | Reserved | Reserved | |||||||
186 | 185 | Reserved | Reserved | |||||||
187 | 186 | Reserved | Reserved | |||||||
188 | 187 | Reserved | Reserved | |||||||
189 | 188 | Reserved | Reserved | |||||||
190 | 189 | Reserved | Reserved | |||||||
191 | 190 | Reserved | Reserved | |||||||
192 | 191 | Reserved | Reserved | |||||||
193 | 192 | Reserved | Reserved | |||||||
194 | 193 | Reserved | Reserved | |||||||
195 | 194 | Reserved | Reserved | |||||||
196 | 195 | Reserved | Reserved | |||||||
197 | 196 | Reserved | Reserved | |||||||
198 | 197 | Reserved | Reserved | |||||||
199 | 198 | Reserved | Reserved | |||||||
200 | 199 | Reserved | Reserved | |||||||
201 | 200 | Reserved | Reserved | |||||||
202 | 201 | Reserved | Reserved | |||||||
203 | 202 | Reserved | Reserved | |||||||
204 | 203 | Reserved | Reserved | |||||||
205 | 204 | Reserved | Reserved | |||||||
206 | 205 | Reserved | Reserved | |||||||
207 | 206 | Reserved | Reserved | |||||||
208 | 207 | Reserved | Reserved | |||||||
209 | 208 | Reserved | Reserved | |||||||
210 | 209 | Reserved | Reserved | |||||||
211 | 210 | HREG_DAY_WC1 | bitfield | 1 | Week timer slot #1 | Week timer 1 Days when allowed. | Days | Bit 0: Sunday <20> Bit 6: Saturday | ||
212 | 211 | HREG_STA_HOUR_WC1 | uint16 | 1 | Week timer 1 Start h | WC1 Start h | WC1 Start h | |||
213 | 212 | HREG_STA_MIN_WC1 | uint16 | 1 | Week timer 1 Start m | WC1 Start m | WC1 Start m | |||
214 | 213 | HREG_STO_HOUR_WC1 | uint16 | 1 | Week timer 1 Stop h | WC1 Stop h | WC1 Stop h | |||
215 | 214 | HREG_STO_MIN_WC1 | uint16 | 1 | Week timer 1 Stop m | WC1 Stop m | WC1 Stop m | |||
216 | 215 | HREG_WC1 | enumeration | 1 | Week timer 1 Function | WC1 Function | WC1 Function | #define TIMER_PROGRAM_OFF 0 #define TIMER_AWAY 1 #define TIMER_AWAY_LONG 2 #define TIMER_HEAT_DIS 3 #define TIMER_COOL_DIS 4 #define TIMER_TEMP_DECR 5 #define TIMER_MAX_H 6 #define TIMER_MAX_C 7 #define TIMER_RELAY 16 #define TIMER_BOOST 17 /* Circulation air state change time program (Pallas) */ #define TIMER_CLOSED_CIRCULATION 18 /* This time program function is relevant in OFFICE program variant (use * method) and it means that the machine should be running (instead of * being in STOP state). */ #define TIMER_RUNTIME 30 | ||
217 | 216 | HREG_DAY_WC2 | bitfield | 1 | Week timer slot #2 | Week timer 2 Days when allowed. | Days | Days | ||
218 | 217 | HREG_STA_HOUR_WC2 | uint16 | 1 | Week timer 2 Start h | WC1 Start h | WC1 Start h | |||
219 | 218 | HREG_STA_MIN_WC2 | uint16 | 1 | Week timer 2 Start m | WC1 Start m | WC1 Start m | |||
220 | 219 | HREG_STO_HOUR_WC2 | uint16 | 1 | Week timer 2 Stop h | WC1 Stop h | WC1 Stop h | |||
221 | 220 | HREG_STO_MIN_WC2 | uint16 | 1 | Week timer 2 Stop m | WC1 Stop m | WC1 Stop m | |||
222 | 221 | HREG_WC2 | enumeration | 1 | Week timer 2 Function | WC1 Function | WC1 Function | |||
223 | 222 | HREG_DAY_WC3 | bitfield | 1 | Week timer slot #3 | Week timer 3 Days when allowed. | Days | Days | ||
224 | 223 | HREG_STA_HOUR_WC3 | uint16 | 1 | Week timer 3 Start h | WC1 Start h | WC1 Start h | |||
225 | 224 | HREG_STA_MIN_WC3 | uint16 | 1 | Week timer 3 Start m | WC1 Start m | WC1 Start m | |||
226 | 225 | HREG_STO_HOUR_WC3 | uint16 | 1 | Week timer 3 Stop h | WC1 Stop h | ||||
227 | 226 | HREG_STO_MIN_WC3 | uint16 | 1 | Week timer 3 Stop m | WC1 Stop m | WC1 Stop m | |||
228 | 227 | HREG_WC3 | enumeration | 1 | Week timer 3 Function | WC1 Function | WC1 Function | |||
229 | 228 | HREG_DAY_WC4 | bitfield | 1 | Week timer slot #4 | Week timer 4 Days when allowed. | Days | Days | ||
230 | 229 | HREG_STA_HOUR_WC4 | uint16 | 1 | Week timer 4 Start h | WC1 Start h | WC1 Start h | |||
231 | 230 | HREG_STA_MIN_WC4 | uint16 | 1 | Week timer 4 Start m | WC1 Start m | WC1 Start m | |||
232 | 231 | HREG_STO_HOUR_WC4 | uint16 | 1 | Week timer 4 Stop h | WC1 Stop h | WC1 Stop h | |||
233 | 232 | HREG_STO_MIN_WC4 | uint16 | 1 | Week timer 4 Stop m | WC1 Stop m | WC1 Stop m | |||
234 | 233 | HREG_WC4 | uint16 | 1 | Week timer 4 Function | |||||
235 | 234 | HREG_DAY_WC5 | bitfield | 1 | Week timer slot #5 | Week timer 5 Days when allowed. | Days | Days | ||
236 | 235 | HREG_STA_HOUR_WC5 | uint16 | 1 | Week timer 5 Start h | WC1 Start h | WC1 Start h | |||
237 | 236 | HREG_STA_MIN_WC5 | uint16 | 1 | Week timer 5 Start m | WC1 Start m | WC1 Start m | |||
238 | 237 | HREG_STO_HOUR_WC5 | uint16 | 1 | Week timer 5 Stop h | WC1 Stop h | WC1 Stop h | |||
239 | 238 | HREG_STO_MIN_WC5 | uint16 | 1 | Week timer 5 Stop m | WC1 Stop m | WC1 Stop m | |||
240 | 239 | HREG_WC5 | uint16 | 1 | Week timer 5 Function | |||||
241 | 240 | HREG_DAY_WC6 | bitfield | 1 | Week timer slot #6 | Week timer 6 Days when allowed. | Days | Days | ||
242 | 241 | HREG_STA_HOUR_WC6 | uint16 | 1 | Week timer 6 Start h | WC1 Start h | WC1 Start h | |||
243 | 242 | HREG_STA_MIN_WC6 | uint16 | 1 | Week timer 6 Start m | |||||
244 | 243 | HREG_STO_HOUR_WC6 | uint16 | 1 | Week timer 6 Stop h | |||||
245 | 244 | HREG_STO_MIN_WC6 | uint16 | 1 | Week timer 6 Stop m | |||||
246 | 245 | HREG_WC6 | uint16 | 1 | Week timer 6 Function | |||||
247 | 246 | HREG_DAY_WC7 | bitfield | 1 | Week timer slot #7 | Week timer 7 Days when allowed. | Days | Days | ||
248 | 247 | HREG_STA_HOUR_WC7 | uint16 | 1 | Week timer 7 Start h | WC1 Start h | WC1 Start h | |||
249 | 248 | HREG_STA_MIN_WC7 | uint16 | 1 | Week timer 7 Start m | |||||
250 | 249 | HREG_STO_HOUR_WC7 | uint16 | 1 | Week timer 7 Stop h | |||||
251 | 250 | HREG_STO_MIN_WC7 | uint16 | 1 | Week timer 7 Stop m | |||||
252 | 251 | HREG_WC7 | uint16 | 1 | undefined | Week timer 7 Function | ||||
253 | 252 | HREG_DAY_WC8 | bitfield | 1 | Week timer slot #8 | Week timer 8 Days when allowed. | Days | Days | ||
254 | 253 | HREG_STA_HOUR_WC8 | uint16 | 1 | Week timer 8 Start h | WC1 Start h | WC1 Start h | |||
255 | 254 | HREG_STA_MIN_WC8 | uint16 | 1 | Week timer 8 Start m | |||||
256 | 255 | HREG_STO_HOUR_WC8 | uint16 | 1 | Week timer 8 Stop h | |||||
257 | 256 | HREG_STO_MIN_WC8 | uint16 | 1 | Week timer 8 Stop m | |||||
258 | 257 | HREG_WC8 | uint16 | 1 | undefined | Week timer 8 Function | ||||
259 | 258 | HREG_DAY_WC9 | bitfield | 1 | Week timer slot #9 | Week timer 9 Days when allowed. | Days | Days | ||
260 | 259 | HREG_STA_HOUR_WC9 | uint16 | 1 | Week timer 9 Start h | |||||
261 | 260 | HREG_STA_MIN_WC9 | uint16 | 1 | Week timer 9 Start m | |||||
262 | 261 | HREG_STO_HOUR_WC9 | uint16 | 1 | Week timer 9 Stop h | |||||
263 | 262 | HREG_STO_MIN_WC9 | uint16 | 1 | Week timer 9 Stop m | |||||
264 | 263 | HREG_WC9 | uint16 | 1 | Week timer 9 Function | |||||
265 | 264 | HREG_DAY_WC10 | bitfield | 1 | Week timer slot #10 | Week timer 10 Days when allowed. | Days | Days | ||
266 | 265 | HREG_STA_HOUR_WC10 | uint16 | 1 | Week timer 10 Start h | |||||
267 | 266 | HREG_STA_MIN_WC10 | uint16 | 1 | Week timer 10 Start m | |||||
268 | 267 | HREG_STO_HOUR_WC10 | uint16 | 1 | Week timer 10 Stop h | |||||
269 | 268 | HREG_STO_MIN_WC10 | uint16 | 1 | Week timer 10 Stop m | |||||
270 | 269 | HREG_WC10 | uint16 | 1 | Week timer 10 Function | |||||
271 | 270 | HREG_DAY_WC11 | bitfield | 1 | Week timer slot #11 | Week timer 11 Days when allowed. | Days | Days | ||
272 | 271 | HREG_STA_HOUR_WC11 | uint16 | 1 | Week timer 11 Start h | |||||
273 | 272 | HREG_STA_MIN_WC11 | uint16 | 1 | Week timer 11 Start m | |||||
274 | 273 | HREG_STO_HOUR_WC11 | uint16 | 1 | Week timer 11 Stop h | |||||
275 | 274 | HREG_STO_MIN_WC11 | uint16 | 1 | Week timer 11 Stop m | |||||
276 | 275 | HREG_WC11 | uint16 | 1 | Week timer 11 Function | |||||
277 | 276 | HREG_DAY_WC12 | bitfield | 1 | Week timer slot #12 | Week timer 12 Days when allowed. | Days | Days | ||
278 | 277 | HREG_STA_HOUR_WC12 | uint16 | 1 | Week timer 12 Start h | |||||
279 | 278 | HREG_STA_MIN_WC12 | uint16 | 1 | Week timer 12 Start m | |||||
280 | 279 | HREG_STO_HOUR_WC12 | uint16 | 1 | Week timer 12 Stop h | |||||
281 | 280 | HREG_STO_MIN_WC12 | uint16 | 1 | Week timer 12 Stop m | |||||
282 | 281 | HREG_WC12 | uint16 | 1 | Week timer 12 Function | |||||
283 | 282 | HREG_DAY_WC13 | bitfield | 1 | Week timer slot #13 | Week timer 13 Days when allowed. | Days | Days | ||
284 | 283 | HREG_STA_HOUR_WC13 | uint16 | 1 | Week timer 13 Start h | |||||
285 | 284 | HREG_STA_MIN_WC13 | uint16 | 1 | Week timer 13 Start m | |||||
286 | 285 | HREG_STO_HOUR_WC13 | uint16 | 1 | Week timer 13 Stop h | |||||
287 | 286 | HREG_STO_MIN_WC13 | uint16 | 1 | Week timer 13 Stop m | |||||
288 | 287 | HREG_WC13 | uint16 | 1 | Week timer 13 Function | |||||
289 | 288 | HREG_DAY_WC14 | bitfield | 1 | Week timer slot #14 | Week timer 14 Days when allowed. | Days | Days | ||
290 | 289 | HREG_STA_HOUR_WC14 | uint16 | 1 | Week timer 14 Start h | |||||
291 | 290 | HREG_STA_MIN_WC14 | uint16 | 1 | Week timer 14 Start m | |||||
292 | 291 | HREG_STO_HOUR_WC14 | uint16 | 1 | Week timer 14 Stop h | |||||
293 | 292 | HREG_STO_MIN_WC14 | uint16 | 1 | Week timer 14 Stop m | |||||
294 | 293 | HREG_WC14 | uint16 | 1 | Week timer 14 Function | |||||
295 | 294 | HREG_DAY_WC15 | bitfield | 1 | Week timer slot #15 | Week timer 15 Days when allowed. | Days | Days | ||
296 | 295 | HREG_STA_HOUR_WC15 | uint16 | 1 | Week timer 15 Start h | |||||
297 | 296 | HREG_STA_MIN_WC15 | uint16 | 1 | Week timer 15 Start m | |||||
298 | 297 | HREG_STO_HOUR_WC15 | uint16 | 1 | Week timer 15 Stop h | |||||
299 | 298 | HREG_STO_MIN_WC15 | uint16 | 1 | Week timer 15 Stop m | |||||
300 | 299 | HREG_WC15 | uint16 | 1 | Week timer 15 Function | |||||
301 | 300 | HREG_DAY_WC16 | bitfield | 1 | Week timer slot #16 | Week timer 16 Days when allowed. | Days | Days | ||
302 | 301 | HREG_STA_HOUR_WC16 | uint16 | 1 | Week timer 16 Start h | |||||
303 | 302 | HREG_STA_MIN_WC16 | uint16 | 1 | Week timer 16 Start m | |||||
304 | 303 | HREG_STO_HOUR_WC16 | uint16 | 1 | Week timer 16 Stop h | |||||
305 | 304 | HREG_STO_MIN_WC16 | uint16 | 1 | Week timer 16 Stop m | |||||
306 | 305 | HREG_WC16 | uint16 | 1 | Week timer 16 Function | |||||
307 | 306 | HREG_DAY_WC17 | bitfield | 1 | Week timer slot #17 | Week timer 17 Days when allowed. | Days | Days | ||
308 | 307 | HREG_STA_HOUR_WC17 | uint16 | 1 | Week timer 17 Start h | |||||
309 | 308 | HREG_STA_MIN_WC17 | uint16 | 1 | Week timer 17 Start m | |||||
310 | 309 | HREG_STO_HOUR_WC17 | uint16 | 1 | Week timer 17 Stop h | |||||
311 | 310 | HREG_STO_MIN_WC17 | uint16 | 1 | Week timer 17 Stop m | |||||
312 | 311 | HREG_WC17 | uint16 | 1 | Week timer 17 Function | |||||
313 | 312 | HREG_DAY_WC18 | bitfield | 1 | Week timer slot #18 | Week timer 18 Days when allowed. | Days | Days | ||
314 | 313 | HREG_STA_HOUR_WC18 | uint16 | 1 | Week timer 18 Start h | |||||
315 | 314 | HREG_STA_MIN_WC18 | uint16 | 1 | Week timer 18 Start m | |||||
316 | 315 | HREG_STO_HOUR_WC18 | uint16 | 1 | Week timer 18 Stop h | |||||
317 | 316 | HREG_STO_MIN_WC18 | uint16 | 1 | Week timer 18 Stop m | |||||
318 | 317 | HREG_WC18 | uint16 | 1 | Week timer 18 Function | |||||
319 | 318 | HREG_DAY_WC19 | bitfield | 1 | Week timer slot #19 | Week timer 19 Days when allowed. | Days | Days | ||
320 | 319 | HREG_STA_HOUR_WC19 | uint16 | 1 | Week timer 19 Start h | |||||
321 | 320 | HREG_STA_MIN_WC19 | uint16 | 1 | Week timer 19 Start m | |||||
322 | 321 | HREG_STO_HOUR_WC19 | uint16 | 1 | Week timer 19 Stop h | |||||
323 | 322 | HREG_STO_MIN_WC19 | uint16 | 1 | Week timer 19 Stop m | |||||
324 | 323 | HREG_WC19 | uint16 | 1 | Week timer 19 Function | |||||
325 | 324 | HREG_DAY_WC20 | bitfield | 1 | Week timer slot #20 | Week timer 20 Days when allowed. | Days | Days | ||
326 | 325 | HREG_STA_HOUR_WC20 | uint16 | 1 | Week timer 20 Start h | |||||
327 | 326 | HREG_STA_MIN_WC20 | uint16 | 1 | Week timer 20 Start m | |||||
328 | 327 | HREG_STO_HOUR_WC20 | uint16 | 1 | Week timer 20 Stop h | |||||
329 | 328 | HREG_STO_MIN_WC20 | uint16 | 1 | Week timer 20 Stop m | |||||
330 | 329 | HREG_WC20 | uint16 | 1 | Week timer 20 Function | |||||
331 | 330 | HREG_STA_PV_Y1 | uint16 | 1 | Year timer slot #1 | Year program 1 start day-of-month | ||||
332 | 331 | HREG_STA_KK_Y1 | uint16 | 1 | Year program 1 stop month | |||||
333 | 332 | HREG_ACTIVE_TIMEPROGRAMS_1 | uint16 | 1 | Active time programs, week slots 1-16 | Active time programs, week slots 1-16 | ||||
334 | 333 | HREG_STA_HOUR_Y1 | uint16 | 1 | Year program 1 start hour | |||||
335 | 334 | HREG_STA_MIN_Y1 | uint16 | 1 | Year program 1 start minute | |||||
336 | 335 | HREG_STO_PV_Y1 | uint16 | 1 | Year program 1 stop day of month | |||||
337 | 336 | HREG_STO_KK_Y1 | uint16 | 1 | Year program 1 stop month | |||||
338 | 337 | HREG_ACTIVE_TIMEPROGRAMS_2 | uint16 | 1 | Active time programs, week slots 17-20 and year slots 1-5 | Active time programs, week slots 17-20 and year slots 1-5 | ||||
339 | 338 | HREG_STO_HOUR_Y1 | uint16 | 1 | Year program 1 stop hour | |||||
340 | 339 | HREG_STO_MIN_Y1 | uint16 | 1 | Year program 1 stop minute | |||||
341 | 340 | HREG_Y1 | uint16 | 1 | Year program 1 action | #define TIMER_PROGRAM_OFF 0 #define TIMER_AWAY 1 #define TIMER_AWAY_LONG 2 #define TIMER_HEAT_DIS 3 #define TIMER_COOL_DIS 4 #define TIMER_TEMP_DECR 5 #define TIMER_MAX_H 6 #define TIMER_MAX_C 7 #define TIMER_RELAY 16 #define TIMER_BOOST 17 /* Circulation air state change time program (Pallas) */ #define TIMER_CLOSED_CIRCULATION 18 /* This time program function is relevant in OFFICE program variant (use * method) and it means that the machine should be running (instead of * being in STOP state). */ #define TIMER_RUNTIME 30 | ||||
342 | 341 | HREG_STA_PV_Y2 | uint16 | 1 | Year timer slot #2 | Year program 2 start day-of-month | ||||
343 | 342 | HREG_STA_KK_Y2 | uint16 | 1 | Year program 2 stop month | |||||
344 | 343 | HREG_UPTIME | uint16 | 1 | System uptime | System uptime | Warning: the count is approximative, it should not be used for time-keeping purposes | |||
345 | 344 | HREG_STA_HOUR_Y2 | uint16 | 1 | Year program 2 start hour | |||||
346 | 345 | HREG_STA_MIN_Y2 | uint16 | 1 | Year program 2 start minute | |||||
347 | 346 | HREG_STO_PV_Y2 | uint16 | 1 | Year program 2 stop day of month | |||||
348 | 347 | HREG_STO_KK_Y2 | uint16 | 1 | Year program 2 stop month | |||||
349 | 348 | Reserved | uint16 | 1 | Number of active panel bus units | Reserved | ||||
350 | 349 | HREG_STO_HOUR_Y2 | uint16 | 1 | Year program 2 stop hour | |||||
351 | 350 | HREG_STO_MIN_Y2 | uint16 | 1 | Year program 2 stop minute | |||||
352 | 351 | HREG_Y2 | uint16 | 1 | Year program 2 action | |||||
353 | 352 | HREG_STA_PV_Y3 | uint16 | 1 | Year timer slot #3 | Year program 3 start day-of-month | ||||
354 | 353 | HREG_STA_KK_Y3 | uint16 | 1 | Year program 3 stop month | |||||
355 | 354 | HREG_BOOTLOADER_VERSION | uint16 | 1 | Bootloader version | Bootloader version | ||||
356 | 355 | HREG_STA_HOUR_Y3 | uint16 | 1 | Year program 3 start hour | |||||
357 | 356 | HREG_STA_MIN_Y3 | uint16 | 1 | Year program 3 start minute | |||||
358 | 357 | HREG_STO_PV_Y3 | uint16 | 1 | Year program 3 stop day of month | |||||
359 | 358 | HREG_STO_KK_Y3 | uint16 | 1 | Year program 3 stop month | |||||
360 | 359 | HREG_FILTER_TEST_HR | uint16 | 1 | Filter test hour | Filter test hour | ||||
361 | 360 | HREG_STO_HOUR_Y3 | uint16 | 1 | Year program 3 stop hour | |||||
362 | 361 | HREG_STO_MIN_Y3 | uint16 | 1 | Year program 3 stop minute | |||||
363 | 362 | HREG_Y3 | uint16 | 1 | Year program 3 action | |||||
364 | 363 | HREG_STA_PV_Y4 | uint16 | 1 | Year timer slot #4 | Year program 4 start day-of-month | ||||
365 | 364 | HREG_STA_KK_Y4 | uint16 | 1 | Year program 4 stop month | |||||
366 | 365 | HREG_FILTER_TEST_DAYS | uint16 | 1 | Filter test day-of-week | Filter test day-of-week | Expressed as a bitfield similar to week time programs | |||
367 | 366 | HREG_STA_HOUR_Y4 | uint16 | 1 | Year program 4 start hour | |||||
368 | 367 | HREG_STA_MIN_Y4 | uint16 | 1 | Year program 4 start minute | |||||
369 | 368 | HREG_STO_PV_Y4 | uint16 | 1 | Year program 4 stop day of month | |||||
370 | 369 | HREG_STO_KK_Y4 | uint16 | 1 | Year program 4 stop month | |||||
371 | 370 | HREG_FILTER_TEST_TF | uint16 | 1 | Filter test TF fan speed | Filter test TF fan speed | During filter test mode TF will run at this constant fanspeed even in constant duct pressure mode. Note that if value is outside range 20-100, 100% will be used | |||
372 | 371 | HREG_STO_HOUR_Y4 | uint16 | 1 | Year program 4 stop hour | |||||
373 | 372 | HREG_STO_MIN_Y4 | uint16 | 1 | Year program 4 stop minute | |||||
374 | 373 | HREG_Y4 | uint16 | 1 | Year program 4 action | |||||
375 | 374 | HREG_STA_PV_Y5 | uint16 | 1 | Year timer slot #5 | Year program 5 start day-of-month | ||||
376 | 375 | HREG_STA_KK_Y5 | uint16 | 1 | Year program 5 stop month | |||||
377 | 376 | HREG_FILTER_TEST_PF | uint16 | 1 | Filter test PF fan speed | Filter test PF fan speed | During filter test mode PF will run at this constant fanspeed even in constant duct pressure mode. Note that if value is outside range 20-100, 100% will be used | |||
378 | 377 | HREG_STA_HOUR_Y5 | uint16 | 1 | Year program 5 start hour | |||||
379 | 378 | HREG_STA_MIN_Y5 | uint16 | 1 | Year program 5 start minute | |||||
380 | 379 | HREG_STO_PV_Y5 | uint16 | 1 | Year program 5 stop day of month | |||||
381 | 380 | HREG_STO_KK_Y5 | uint16 | 1 | Year program 5 stop month | |||||
382 | 381 | Reserved | Reserved | |||||||
383 | 382 | HREG_STO_HOUR_Y5 | uint16 | 1 | Year program 5 stop hour | |||||
384 | 383 | HREG_STO_MIN_Y5 | uint16 | 1 | Year program 5 stop minute | |||||
385 | 384 | HREG_Y5 | uint16 | 1 | Year program 5 action | |||||
386 | 385 | HREG_ALARM1_ALMTYPE | uint16 | 1 | Alarm log entry #1 | Alarm 1 (newest) alarm type | Alarm 1 (newest) alarm type | ALARM_TE05_L = 1, ALARM_TE10_L = 2, ALARM_TE10_H = 3, ALARM_TE20_H = 4, ALARM_TE30_L = 5, ALARM_TE30_H = 6, ALARM_HP = 7, /* This is both HP and MDX */ ALARM_SLP = 8, ALARM_TE45_L = 9, ALARM_LTO = 10, ALARM_COOL = 11, ALARM_EMERGENCY_STOP = 12 , ALARM_EXTERNAL = 13, /** This used to be ALARM_FIRE on EDA */ ALARM_SERVICE =14 , ALARM_PDS10 = 15, ALARM_SPLY_FILT_H = 16, ALARM_EXT_FILT_H = 17, ALARM_SPLY_FILT_L = 18 , /* This alarm is actually not in use. It is relevant only for large machines with 2-speed fan control */ ALARM_EXT_FILT_L = 19 , /* This alarm is actually not in use. It is relevant only for large machines with 2-speed fan control */ ALARM_TF_PRES = 20, ALARM_PF_PRES = 21 , ALARM_TE50_H = 22, ALARM_TE52_H = 24, ALARM_TF_ROTATION = 25, ALARM_PF_ROTATION = 26, ALARM_TE02_H = 27, ALARM_SERVICE_CONSTANT_DUCT_PRES = 28, /* Under constant duct pressure control, Service alarm is triggered then fanspeeds reach a defined limit */ | ||
387 | 386 | HREG_ALARM1_STATECLASS | uint16 | 1 | Alarm 1 This defines the status (low byte) of the alarm | ALARM_STATE_OFF = 0, ALARM_STATE_ACKED = 1, ALARM_STATE_ON = 2. Write <20>1<93> or <20>2<93> to this register to acknowledge the alarm. | ||||
388 | 387 | HREG_ALARM1_YY | uint16 | 1 | Alarm 1 Alarm year | |||||
389 | 388 | HREG_ALARM1_MM | uint16 | 1 | Alarm 1 Alarm month | |||||
390 | 389 | HREG_ALARM1_DD | uint16 | 1 | Alarm 1 Alarm day. | |||||
391 | 390 | HREG_ALARM1_HH | uint16 | 1 | Alarm 1 Alarm hour | |||||
392 | 391 | HREG_ALARM1_MI | uint16 | 1 | Alarm 1 Alarm minutes | |||||
393 | 392 | HREG_ALARM2_ALMTYPE | uint16 | 1 | Alarm log entry #2 | Alarm 2 (newest) alarm type | ||||
394 | 393 | HREG_ALARM2_STATECLASS | uint16 | 1 | Alarm 2 This defines the status (low byte) of the alarm | |||||
395 | 394 | HREG_ALARM2_YY | uint16 | 1 | Alarm 2 Alarm year | |||||
396 | 395 | HREG_ALARM2_MM | uint16 | 1 | Alarm 2 Alarm month | |||||
397 | 396 | HREG_ALARM2_DD | uint16 | 1 | Alarm 2 Alarm day. | |||||
398 | 397 | HREG_ALARM2_HH | uint16 | 1 | Alarm 2 Alarm hour | |||||
399 | 398 | HREG_ALARM2_MI | uint16 | 1 | Alarm 2 Alarm minutes | |||||
400 | 399 | HREG_ALARM3_ALMTYPE | uint16 | 1 | Alarm log entry #3 | Alarm 3 (newest) alarm type | ||||
401 | 400 | HREG_ALARM3_STATECLASS | uint16 | 1 | Alarm 3 This defines the status (low byte) of the alarm | |||||
402 | 401 | HREG_ALARM3_YY | uint16 | 1 | Alarm 3 Alarm year | |||||
403 | 402 | HREG_ALARM3_MM | uint16 | 1 | Alarm 3 Alarm month | |||||
404 | 403 | HREG_ALARM3_DD | uint16 | 1 | Alarm 3 Alarm day. | |||||
405 | 404 | HREG_ALARM3_HH | uint16 | 1 | Alarm 3 Alarm hour | |||||
406 | 405 | HREG_ALARM3_MI | uint16 | 1 | Alarm 3 Alarm minutes | |||||
407 | 406 | HREG_ALARM4_ALMTYPE | uint16 | 1 | Alarm log entry #4 | Alarm 4 (newest) alarm type | ||||
408 | 407 | HREG_ALARM4_STATECLASS | uint16 | 1 | Alarm 4 This defines the status (low byte) of the alarm | |||||
409 | 408 | HREG_ALARM4_YY | uint16 | 1 | Alarm 4 Alarm year | |||||
410 | 409 | HREG_ALARM4_MM | uint16 | 1 | Alarm 4 Alarm month | |||||
411 | 410 | HREG_ALARM4_DD | uint16 | 1 | Alarm 4 Alarm day. | |||||
412 | 411 | HREG_ALARM4_HH | uint16 | 1 | Alarm 4 Alarm hour | |||||
413 | 412 | HREG_ALARM4_MI | uint16 | 1 | Alarm 4 Alarm minutes | |||||
414 | 413 | HREG_ALARM5_ALMTYPE | uint16 | 1 | Alarm log entry #5 | Alarm 5 (newest) alarm type | ||||
415 | 414 | HREG_ALARM5_STATECLASS | uint16 | 1 | Alarm 5 This defines the status (low byte) of the alarm | |||||
416 | 415 | HREG_ALARM5_YY | uint16 | 1 | Alarm 5 Alarm year | |||||
417 | 416 | HREG_ALARM5_MM | uint16 | 1 | Alarm 5 Alarm month | |||||
418 | 417 | HREG_ALARM5_DD | uint16 | 1 | Alarm 5 Alarm day. | |||||
419 | 418 | HREG_ALARM5_HH | uint16 | 1 | Alarm 5 Alarm hour | |||||
420 | 419 | HREG_ALARM5_MI | uint16 | 1 | Alarm 5 Alarm minutes | |||||
421 | 420 | HREG_ALARM6_ALMTYPE | uint16 | 1 | Alarm log entry #6 | Alarm 6 (newest) alarm type | ||||
422 | 421 | HREG_ALARM6_STATECLASS | uint16 | 1 | Alarm 6 This defines the status (low byte) of the alarm | |||||
423 | 422 | HREG_ALARM6_YY | uint16 | 1 | Alarm 6 Alarm year | |||||
424 | 423 | HREG_ALARM6_MM | uint16 | 1 | Alarm 6 Alarm month | |||||
425 | 424 | HREG_ALARM6_DD | uint16 | 1 | Alarm 6 Alarm day. | |||||
426 | 425 | HREG_ALARM6_HH | uint16 | 1 | Alarm 6 Alarm hour | |||||
427 | 426 | HREG_ALARM6_MI | uint16 | 1 | Alarm 6 Alarm minutes | |||||
428 | 427 | HREG_ALARM7_ALMTYPE | uint16 | 1 | Alarm log entry #7 | Alarm 7 (newest) alarm type | ||||
429 | 428 | HREG_ALARM7_STATECLASS | uint16 | 1 | Alarm 7 This defines the status (low byte) of the alarm | |||||
430 | 429 | HREG_ALARM7_YY | uint16 | 1 | Alarm 7 Alarm year | |||||
431 | 430 | HREG_ALARM7_MM | uint16 | 1 | Alarm 7 Alarm month | |||||
432 | 431 | HREG_ALARM7_DD | uint16 | 1 | Alarm 7 Alarm day. | |||||
433 | 432 | HREG_ALARM7_HH | uint16 | 1 | Alarm 7 Alarm hour | |||||
434 | 433 | HREG_ALARM7_MI | uint16 | 1 | Alarm 7 Alarm minutes | |||||
435 | 434 | HREG_ALARM8_ALMTYPE | uint16 | 1 | Alarm log entry #8 | Alarm 8 (newest) alarm type | ||||
436 | 435 | HREG_ALARM8_STATECLASS | uint16 | 1 | Alarm 8 This defines the status (low byte) of the alarm | |||||
437 | 436 | HREG_ALARM8_YY | uint16 | 1 | Alarm 8 Alarm year | |||||
438 | 437 | HREG_ALARM8_MM | uint16 | 1 | Alarm 8 Alarm month | |||||
439 | 438 | HREG_ALARM8_DD | uint16 | 1 | Alarm 8 Alarm day. | |||||
440 | 439 | HREG_ALARM8_HH | uint16 | 1 | Alarm 8 Alarm hour | |||||
441 | 440 | HREG_ALARM8_MI | uint16 | 1 | Alarm 8 Alarm minutes | |||||
442 | 441 | HREG_ALARM9_ALMTYPE | uint16 | 1 | Alarm log entry #9 | Alarm 9 (newest) alarm type | ||||
443 | 442 | HREG_ALARM9_STATECLASS | uint16 | 1 | Alarm 9 This defines the status (low byte) of the alarm | |||||
444 | 443 | HREG_ALARM9_YY | uint16 | 1 | Alarm 9 Alarm year | |||||
445 | 444 | HREG_ALARM9_MM | uint16 | 1 | Alarm 9 Alarm month | |||||
446 | 445 | HREG_ALARM9_DD | uint16 | 1 | Alarm 9 Alarm day. | |||||
447 | 446 | HREG_ALARM9_HH | uint16 | 1 | Alarm 9 Alarm hour | |||||
448 | 447 | HREG_ALARM9_MI | uint16 | 1 | Alarm 9 Alarm minutes | |||||
449 | 448 | HREG_ALARM10_ALMTYPE | uint16 | 1 | Alarm log entry #10 | Alarm 10 (newest) alarm type | ||||
450 | 449 | HREG_ALARM10_STATECLASS | uint16 | 1 | Alarm 10 This defines the status (low byte) of the alarm | |||||
451 | 450 | HREG_ALARM10_YY | uint16 | 1 | Alarm 10 Alarm year | |||||
452 | 451 | HREG_ALARM10_MM | uint16 | 1 | Alarm 10 Alarm month | |||||
453 | 452 | HREG_ALARM10_DD | uint16 | 1 | Alarm 10 Alarm day. | |||||
454 | 453 | HREG_ALARM10_HH | uint16 | 1 | Alarm 10 Alarm hour | |||||
455 | 454 | HREG_ALARM10_MI | uint16 | 1 | Alarm 10 Alarm minutes | |||||
456 | 455 | HREG_ALARM11_ALMTYPE | uint16 | 1 | Alarm log entry #11 | Alarm 11 (newest) alarm type | ||||
457 | 456 | HREG_ALARM11_STATECLASS | uint16 | 1 | Alarm 11 This defines the status (low byte) of the alarm | |||||
458 | 457 | HREG_ALARM11_YY | uint16 | 1 | Alarm 11 Alarm year | |||||
459 | 458 | HREG_ALARM11_MM | uint16 | 1 | Alarm 11 Alarm month | |||||
460 | 459 | HREG_ALARM11_DD | uint16 | 1 | Alarm 11 Alarm day. | |||||
461 | 460 | HREG_ALARM11_HH | uint16 | 1 | Alarm 11 Alarm hour | |||||
462 | 461 | HREG_ALARM11_MI | uint16 | 1 | Alarm 11 Alarm minutes | |||||
463 | 462 | HREG_ALARM12_ALMTYPE | uint16 | 1 | Alarm log entry #12 | Alarm 12 (newest) alarm type | ||||
464 | 463 | HREG_ALARM12_STATECLASS | uint16 | 1 | Alarm 12 This defines the status (low byte) of the alarm | |||||
465 | 464 | HREG_ALARM12_YY | uint16 | 1 | Alarm 12 Alarm year | |||||
466 | 465 | HREG_ALARM12_MM | uint16 | 1 | Alarm 12 Alarm month | |||||
467 | 466 | HREG_ALARM12_DD | uint16 | 1 | Alarm 12 Alarm day. | |||||
468 | 467 | HREG_ALARM12_HH | uint16 | 1 | Alarm 12 Alarm hour | |||||
469 | 468 | HREG_ALARM12_MI | uint16 | 1 | Alarm 12 Alarm minutes | |||||
470 | 469 | HREG_ALARM13_ALMTYPE | uint16 | 1 | Alarm log entry #13 | Alarm 13 (newest) alarm type | ||||
471 | 470 | HREG_ALARM13_STATECLASS | uint16 | 1 | Alarm 13 This defines the status (low byte) of the alarm | |||||
472 | 471 | HREG_ALARM13_YY | uint16 | 1 | Alarm 13 Alarm year | |||||
473 | 472 | HREG_ALARM13_MM | uint16 | 1 | Alarm 13 Alarm month | |||||
474 | 473 | HREG_ALARM13_DD | uint16 | 1 | Alarm 13 Alarm day. | |||||
475 | 474 | HREG_ALARM13_HH | uint16 | 1 | Alarm 13 Alarm hour | |||||
476 | 475 | HREG_ALARM13_MI | uint16 | 1 | Alarm 13 Alarm minutes | |||||
477 | 476 | HREG_ALARM14_ALMTYPE | uint16 | 1 | Alarm log entry #14 | Alarm 14 (newest) alarm type | ||||
478 | 477 | HREG_ALARM14_STATECLASS | uint16 | 1 | Alarm 14 This defines the status (low byte) of the alarm | |||||
479 | 478 | HREG_ALARM14_YY | uint16 | 1 | Alarm 14 Alarm year | |||||
480 | 479 | HREG_ALARM14_MM | uint16 | 1 | Alarm 14 Alarm month | |||||
481 | 480 | HREG_ALARM14_DD | uint16 | 1 | Alarm 14 Alarm day. | |||||
482 | 481 | HREG_ALARM14_HH | uint16 | 1 | Alarm 14 Alarm hour | |||||
483 | 482 | HREG_ALARM14_MI | uint16 | 1 | Alarm 14 Alarm minutes | |||||
484 | 483 | HREG_ALARM15_ALMTYPE | uint16 | 1 | Alarm log entry #15 | Alarm 15 (newest) alarm type | ||||
485 | 484 | HREG_ALARM15_STATECLASS | uint16 | 1 | Alarm 15 This defines the status (low byte) of the alarm | |||||
486 | 485 | HREG_ALARM15_YY | uint16 | 1 | Alarm 15 Alarm year | |||||
487 | 486 | HREG_ALARM15_MM | uint16 | 1 | Alarm 15 Alarm month | |||||
488 | 487 | HREG_ALARM15_DD | uint16 | 1 | Alarm 15 Alarm day. | |||||
489 | 488 | HREG_ALARM15_HH | uint16 | 1 | Alarm 15 Alarm hour | |||||
490 | 489 | HREG_ALARM15_MI | uint16 | 1 | Alarm 15 Alarm minutes | |||||
491 | 490 | HREG_ALARM16_ALMTYPE | uint16 | 1 | Alarm log entry #16 | Alarm 16 (newest) alarm type | ||||
492 | 491 | HREG_ALARM16_STATECLASS | uint16 | 1 | Alarm 16 This defines the status (low byte) of the alarm | |||||
493 | 492 | HREG_ALARM16_YY | uint16 | 1 | Alarm 16 Alarm year | |||||
494 | 493 | HREG_ALARM16_MM | uint16 | 1 | Alarm 16 Alarm month | |||||
495 | 494 | HREG_ALARM16_DD | uint16 | 1 | Alarm 16 Alarm day. | |||||
496 | 495 | HREG_ALARM16_HH | uint16 | 1 | Alarm 16 Alarm hour | |||||
497 | 496 | HREG_ALARM16_MI | uint16 | 1 | Alarm 16 Alarm minutes | |||||
498 | 497 | HREG_ALARM17_ALMTYPE | uint16 | 1 | Alarm log entry #17 | Alarm 17 (newest) alarm type | ||||
499 | 498 | HREG_ALARM17_STATECLASS | uint16 | 1 | Alarm 17 This defines the status (low byte) of the alarm | |||||
500 | 499 | HREG_ALARM17_YY | uint16 | 1 | Alarm 17 Alarm year | |||||
501 | 500 | HREG_ALARM17_MM | uint16 | 1 | Alarm 17 Alarm month | |||||
502 | 501 | HREG_ALARM17_DD | uint16 | 1 | Alarm 17 Alarm day. | |||||
503 | 502 | HREG_ALARM17_HH | uint16 | 1 | Alarm 17 Alarm hour | |||||
504 | 503 | HREG_ALARM17_MI | uint16 | 1 | Alarm 17 Alarm minutes | |||||
505 | 504 | HREG_ALARM18_ALMTYPE | uint16 | 1 | Alarm log entry #18 | Alarm 18 (newest) alarm type | ||||
506 | 505 | HREG_ALARM18_STATECLASS | uint16 | 1 | Alarm 18 This defines the status (low byte) of the alarm | |||||
507 | 506 | HREG_ALARM18_YY | uint16 | 1 | Alarm 18 Alarm year | |||||
508 | 507 | HREG_ALARM18_MM | uint16 | 1 | Alarm 18 Alarm month | |||||
509 | 508 | HREG_ALARM18_DD | uint16 | 1 | Alarm 18 Alarm day. | |||||
510 | 509 | HREG_ALARM18_HH | uint16 | 1 | Alarm 18 Alarm hour | |||||
511 | 510 | HREG_ALARM18_MI | uint16 | 1 | Alarm 18 Alarm minutes | |||||
512 | 511 | HREG_ALARM19_ALMTYPE | uint16 | 1 | Alarm log entry #19 | Alarm 19 (newest) alarm type | ||||
513 | 512 | HREG_ALARM19_STATECLASS | uint16 | 1 | Alarm 19 This defines the status (low byte) of the alarm | |||||
514 | 513 | HREG_ALARM19_YY | uint16 | 1 | Alarm 19 Alarm year | |||||
515 | 514 | HREG_ALARM19_MM | uint16 | 1 | Alarm 19 Alarm month | |||||
516 | 515 | HREG_ALARM19_DD | uint16 | 1 | Alarm 19 Alarm day. | |||||
517 | 516 | HREG_ALARM19_HH | uint16 | 1 | Alarm 19 Alarm hour | |||||
518 | 517 | HREG_ALARM19_MI | uint16 | 1 | Alarm 19 Alarm minutes | |||||
519 | 518 | HREG_ALARM20_ALMTYPE | uint16 | 1 | Alarm log entry #20 | Alarm 20 (newest) alarm type | ||||
520 | 519 | HREG_ALARM20_STATECLASS | uint16 | 1 | Alarm 20 This defines the status (low byte) of the alarm | |||||
521 | 520 | HREG_ALARM20_YY | uint16 | 1 | Alarm 20 Alarm year | |||||
522 | 521 | HREG_ALARM20_MM | uint16 | 1 | Alarm 20 Alarm month | |||||
523 | 522 | HREG_ALARM20_DD | uint16 | 1 | Alarm 20 Alarm day. | |||||
524 | 523 | HREG_ALARM20_HH | uint16 | 1 | Alarm 20 Alarm hour | |||||
525 | 524 | HREG_ALARM20_MI | uint16 | 1 | Alarm 20 Alarm minutes | |||||
526 | 525 | Reserved | Reserved | |||||||
527 | 526 | Reserved | Reserved | |||||||
528 | 527 | Reserved | Reserved | |||||||
529 | 528 | Reserved | Reserved | |||||||
530 | 529 | Reserved | Reserved | |||||||
531 | 530 | Reserved | Reserved | |||||||
532 | 531 | Reserved | Reserved | |||||||
533 | 532 | Reserved | Reserved | |||||||
534 | 533 | Reserved | Reserved | |||||||
535 | 534 | Reserved | Reserved | |||||||
536 | 535 | Reserved | Reserved | |||||||
537 | 536 | Reserved | Reserved | |||||||
538 | 537 | Reserved | Reserved | |||||||
539 | 538 | HREG_ALARM_SERVICE_TIME | uint16 | 1 | Service reminder | Number of days until service reminder alarm is signaled. | Service reminder | Number of days until service reminder alarm is given | ||
540 | 539 | Reserved | Reserved | |||||||
541 | 540 | Reserved | Reserved | |||||||
542 | 541 | Reserved | Reserved | |||||||
543 | 542 | Reserved | Reserved | |||||||
544 | 543 | Reserved | Reserved | |||||||
545 | 544 | Reserved | Reserved | |||||||
546 | 545 | Reserved | Reserved | |||||||
547 | 546 | Reserved | Reserved | |||||||
548 | 547 | Reserved | Reserved | |||||||
549 | 548 | Reserved | Reserved | |||||||
550 | 549 | Reserved | Reserved | |||||||
551 | 550 | Reserved | Reserved | |||||||
552 | 551 | Reserved | Reserved | |||||||
553 | 552 | Reserved | Reserved | |||||||
554 | 553 | Reserved | Reserved | |||||||
555 | 554 | Reserved | Reserved | |||||||
556 | 555 | Reserved | Reserved | |||||||
557 | 556 | Reserved | Reserved | |||||||
558 | 557 | Reserved | Reserved | |||||||
559 | 558 | Reserved | Reserved | |||||||
560 | 559 | Reserved | Reserved | |||||||
561 | 560 | Reserved | Reserved | |||||||
562 | 561 | Reserved | Reserved | |||||||
563 | 562 | Reserved | Reserved | |||||||
564 | 563 | Reserved | Reserved | |||||||
565 | 564 | Reserved | Reserved | |||||||
566 | 565 | Reserved | Reserved | |||||||
567 | 566 | Reserved | Reserved | |||||||
568 | 567 | Reserved | Reserved | |||||||
569 | 568 | Reserved | Reserved | |||||||
570 | 569 | Reserved | Reserved | |||||||
571 | 570 | Reserved | Reserved | |||||||
572 | 571 | Reserved | Reserved | |||||||
573 | 572 | Reserved | Reserved | |||||||
574 | 573 | Reserved | Reserved | |||||||
575 | 574 | Reserved | Reserved | |||||||
576 | 575 | Reserved | Reserved | |||||||
577 | 576 | Reserved | Reserved | |||||||
578 | 577 | Reserved | Reserved | |||||||
579 | 578 | HREG_B_ALARM_START | uint16 | 1 | Start time | B alarm relay signaling allowed start hour. | Start time | Allowed start time for B alarm output | The defined time is HH:00, where HH is the register's value | |
580 | 579 | HREG_B_ALARM_STOP | uint16 | 1 | Ending time | B alarm relay signaling allowed stop hour. | Ending time | Allowed stop time for B alarm output | The defined time is HH:00, where HH is the register's value | |
581 | 580 | HREG_B_ALARM_WEEKDAYS | bitfield | 1 | Weekdays | B alarm relay signaling allowed weekdays (bitmap, stored in low 7 bits of the register). | Weekdays | Choose allowed weekdays for B alarm output | Bit 0: Sunday <20> Bit 6: Saturday | |
582 | 581 | HREG_N_O_ALARMS | uint16 | 1 | Number of alarms | Current number of alarms in the alarm log. | Number of alarms | Current number of alarms in the alarm log | ||
583 | 582 | HREG_C_MIN_RTC | uint16 | 1 | RTC interface for changing minutes field | |||||
584 | 583 | HREG_C_HOUR_RTC | uint16 | 1 | RTC interface for changing hour field | |||||
585 | 584 | HREG_C_DAY_RTC | uint16 | 1 | RTC interface for changing day of month field | |||||
586 | 585 | HREG_C_MONTH_RTC | uint16 | 1 | RTC interface for changing month field | |||||
587 | 586 | HREG_C_YEAR_RTC | uint16 | 1 | RTC interface for changing year field | |||||
588 | 587 | Reserved | Reserved | |||||||
589 | 588 | Reserved | Reserved | |||||||
590 | 589 | Reserved | Reserved | |||||||
591 | 590 | Reserved | Reserved | |||||||
592 | 591 | Reserved | Reserved | |||||||
593 | 592 | Reserved | Reserved | |||||||
594 | 593 | Reserved | Reserved | |||||||
595 | 594 | Reserved | Reserved | |||||||
596 | 595 | Reserved | Reserved | |||||||
597 | 596 | Reserved | Reserved | |||||||
598 | 597 | HREG_FAMILY_TYPE | uint16 | 1 | Family | Machine family type | Family | Machine family type | ||
599 | 598 | HREG_HW_VERSION | enumeration | 1 | Hardware version | Hardware version desc | MD Hardware version | Unit motherboard hardware version | Value 1 corresponds to Rev.A, value 2 is B, value is C and so forth up to 27 which is Rev.Z | |
600 | 599 | HREG_SW_VERSION | uint16 | 100 | MD SW version | MD Software release number | MD SW version | Unit motherboard software version | ||
601 | 600 | Reserved | Reserved | |||||||
602 | 601 | Reserved | Reserved | |||||||
603 | 602 | Reserved | Reserved | |||||||
604 | 603 | Reserved | Reserved | |||||||
605 | 604 | Reserved | Reserved | |||||||
606 | 605 | Reserved | Reserved | |||||||
607 | 606 | Reserved | Reserved | |||||||
608 | 607 | Reserved | Reserved | |||||||
609 | 608 | Reserved | Reserved | |||||||
610 | 609 | Reserved | Reserved | |||||||
611 | 610 | Reserved | Reserved | |||||||
612 | 611 | Reserved | Reserved | |||||||
613 | 612 | Reserved | Reserved | |||||||
614 | 613 | Reserved | Reserved | |||||||
615 | 614 | Reserved | Reserved | |||||||
616 | 615 | Reserved | Reserved | |||||||
617 | 616 | Reserved | Reserved | |||||||
618 | 617 | Reserved | Reserved | |||||||
619 | 618 | Reserved | Reserved | |||||||
620 | 619 | Reserved | Reserved | |||||||
621 | 620 | Reserved | Reserved | |||||||
622 | 621 | Reserved | Reserved | |||||||
623 | 622 | Reserved | Reserved | |||||||
624 | 623 | Reserved | Reserved | |||||||
625 | 624 | Reserved | Reserved | |||||||
626 | 625 | Reserved | Reserved | |||||||
627 | 626 | Reserved | Reserved | |||||||
628 | 627 | Reserved | Reserved | |||||||
629 | 628 | Reserved | Reserved | |||||||
630 | 629 | Reserved | Reserved | |||||||
631 | 630 | Reserved | Reserved | |||||||
632 | 631 | Reserved | Reserved | |||||||
633 | 632 | Reserved | Reserved | |||||||
634 | 633 | Reserved | Reserved | |||||||
635 | 634 | Reserved | Reserved | |||||||
636 | 635 | Reserved | Reserved | |||||||
637 | 636 | Reserved | Reserved | |||||||
638 | 637 | Reserved | Reserved | |||||||
639 | 638 | Reserved | Reserved | |||||||
640 | 639 | Reserved | Reserved | |||||||
641 | 640 | HREG_MBADDR | uint16 | 1 | 1 - 100 | Modbus id | Modbus address used by the card. | Modbus id | MD card modbus address 1 - 100 | |
642 | 641 | Reserved | Reserved | |||||||
643 | 642 | Reserved | Reserved | |||||||
644 | 643 | Reserved | Reserved | |||||||
645 | 644 | Reserved | Reserved | |||||||
646 | 645 | Reserved | Reserved | |||||||
647 | 646 | Reserved | Reserved | |||||||
648 | 647 | Reserved | Reserved | |||||||
649 | 648 | Reserved | Reserved | |||||||
650 | 649 | Reserved | Reserved | |||||||
651 | 650 | Reserved | Reserved | |||||||
652 | 651 | Reserved | Reserved | |||||||
653 | 652 | Reserved | Reserved | |||||||
654 | 653 | Reserved | Reserved | |||||||
655 | 654 | HREG_IPADDR_HIGH | uint16 | 1 | IP address | IP address high bytes Useful values: 192.168 would be 49320 | IP address | Calculate this as A*2^8+B for IP addr starting with bytes A.B | ||
656 | 655 | HREG_IPADDR_LOW | uint16 | 1 | IP address | IP address low bytes | IP address | : Calculate this as C*2^8+D for IP addr ending with bytes C.D | ||
657 | 656 | HREG_GWIPADDR_HIGH | uint16 | 1 | Gateway IP address | Gateway IP address low bytes Note: useful values: 192.168 would be 49320 | Calculate this as A*2^8+B for gateway IP addr starting with bytes A.B | |||
658 | 657 | HREG_GWIPADDR_LOW | uint16 | 1 | Gateway IP address | Gateway IP address low bytes/ | : Calculate this as C*2^8+D for gateway IP addr ending with bytes C.D | |||
659 | 658 | HREG_NETMASK_HIGH | uint16 | 1 | Netmask | Netmask high bytes Note: useful value 65535, for bytes 255.255 | : Calculate this as A*2^8+B for netmask starting with bytes A.B | |||
660 | 659 | HREG_NETMASK_LOW | uint16 | 1 | Netmask | Netmask low bytes Note: useful value 65280, for bytes 255.0 | : Calculate this as C*2^8+D for netmask ending with bytes C.D | |||
661 | 660 | HREG_DNSIP_ADDR_HIGH | uint16 | 1 | DNS server address | DNS server IP high bytes | : Calculate this as A*2^8+B for ip starting with bytes A.B | |||
662 | 661 | HREG_DNSIP_ADDR_LOW | uint16 | 1 | DNS server address | DNS server IP low bytes | : Calculate this as C*2^8+D for ip ending with bytes C.D | |||
663 | 662 | Reserved | Reserved | |||||||
664 | 663 | Reserved | Reserved | |||||||
665 | 664 | Reserved | Reserved | |||||||
666 | 665 | Reserved | Reserved | |||||||
667 | 666 | Reserved | Reserved | |||||||
668 | 667 | HREG_DHCP_CONTROL | enumeration | 1 | DHCP | Dynamic Host Configuration Protocol | Value of 0 indicates DHCP is active, value of 1 indicates DHCP inactive. | |||
669 | 668 | Reserved | Reserved | |||||||
670 | 669 | Reserved | Reserved | |||||||
671 | 670 | Reserved | Reserved | |||||||
672 | 671 | Reserved | Reserved | |||||||
673 | 672 | Reserved | Reserved | |||||||
674 | 673 | Reserved | Reserved | |||||||
675 | 674 | Reserved | Reserved | |||||||
676 | 675 | Reserved | Reserved | |||||||
677 | 676 | Reserved | Reserved | |||||||
678 | 677 | Reserved | Reserved | |||||||
679 | 678 | Reserved | Reserved | |||||||
680 | 679 | Reserved | Reserved | |||||||
681 | 680 | Reserved | Reserved | |||||||
682 | 681 | Reserved | Reserved | |||||||
683 | 682 | Reserved | Reserved | |||||||
684 | 683 | Reserved | Reserved | |||||||
685 | 684 | Reserved | Reserved | |||||||
686 | 685 | Reserved | Reserved | |||||||
687 | 686 | Reserved | Reserved | |||||||
688 | 687 | Reserved | Reserved | |||||||
689 | 688 | Reserved | Reserved | |||||||
690 | 689 | Reserved | Reserved | |||||||
691 | 690 | Reserved | Reserved | |||||||
692 | 691 | Reserved | Reserved | |||||||
693 | 692 | Reserved | Reserved | |||||||
694 | 693 | Reserved | Reserved | |||||||
695 | 694 | Reserved | Reserved | |||||||
696 | 695 | Reserved | Reserved | |||||||
697 | 696 | Reserved | Reserved | |||||||
698 | 697 | Reserved | Reserved | |||||||
699 | 698 | Reserved | Reserved | |||||||
700 | 699 | Reserved | Reserved | |||||||
701 | 700 | Reserved | Reserved | |||||||
702 | 701 | Reserved | Reserved | |||||||
703 | 702 | Reserved | Reserved | |||||||
704 | 703 | Reserved | Reserved | |||||||
705 | 704 | Reserved | Reserved | |||||||
706 | 705 | Reserved | Reserved | |||||||
707 | 706 | Reserved | Reserved | |||||||
708 | 707 | Reserved | Reserved | |||||||
709 | 708 | Reserved | Reserved | |||||||
710 | 709 | Reserved | Reserved | |||||||
711 | 710 | Reserved | Reserved | |||||||
712 | 711 | Reserved | Reserved | |||||||
713 | 712 | Reserved | Reserved | |||||||
714 | 713 | Reserved | Reserved | |||||||
715 | 714 | Reserved | Reserved | |||||||
716 | 715 | Reserved | Reserved | |||||||
717 | 716 | Reserved | Reserved | |||||||
718 | 717 | Reserved | Reserved | |||||||
719 | 718 | Reserved | Reserved | |||||||
720 | 719 | Reserved | Reserved | |||||||
721 | 720 | Reserved | Reserved | |||||||
722 | 721 | Reserved | Reserved | |||||||
723 | 722 | Reserved | Reserved | |||||||
724 | 723 | Reserved | Reserved | |||||||
725 | 724 | Reserved | Reserved | |||||||
726 | 725 | Reserved | Reserved | |||||||
727 | 726 | Reserved | Reserved | |||||||
728 | 727 | Reserved | Reserved | |||||||
729 | 728 | Reserved | Reserved | |||||||
730 | 729 | Reserved | Reserved | |||||||
731 | 730 | Reserved | Reserved | |||||||
732 | 731 | Reserved | Reserved | |||||||
733 | 732 | Reserved | Reserved | |||||||
734 | 733 | HREG_MODBUS_SPEED | enumeration | 1 | Modbus speed | Modbus RTU serial line speed | Modbus speed | Modbus RTU serial line speed | SPEED_9600 = 6, SPEED_19200 = 7, SPEED_115200 = 10 | |
735 | 734 | HREG_MODBUS_PARITY | enumeration | 1 | Modbus parity | Modbus RTU serial line parity | Modbus parity | Modbus RTU serial line parity | PARITY_NONE = 1, PARITY_EVEN = 2 | |
736 | 735 | Reserved | Reserved | |||||||
737 | 736 | Reserved | Reserved | |||||||
738 | 737 | Reserved | Reserved | |||||||
739 | 738 | Reserved | Reserved | |||||||
740 | 739 | Reserved | Reserved | |||||||
741 | 740 | Reserved | Reserved | |||||||
742 | 741 | Reserved | Reserved | |||||||
743 | 742 | Reserved | Reserved | |||||||
744 | 743 | Reserved | Reserved | |||||||
745 | 744 | Reserved | Reserved | |||||||
746 | 745 | Reserved | Reserved | |||||||
747 | 746 | Reserved | Reserved | |||||||
748 | 747 | Reserved | Reserved | |||||||
749 | 748 | Reserved | Reserved | |||||||
750 | 749 | Reserved | Reserved | |||||||
751 | 750 | Reserved | Reserved | |||||||
752 | 751 | Reserved | Reserved | |||||||
753 | 752 | Reserved | Reserved | |||||||
754 | 753 | Reserved | Reserved | |||||||
755 | 754 | Reserved | Reserved | |||||||
756 | 755 | Reserved | Reserved | |||||||
757 | 756 | Reserved | Reserved | |||||||
758 | 757 | Reserved | Reserved | |||||||
759 | 758 | Reserved | Reserved | |||||||
760 | 759 | Reserved | Reserved | |||||||
761 | 760 | Reserved | Reserved | |||||||
762 | 761 | Reserved | Reserved | |||||||
763 | 762 | Reserved | Reserved | |||||||
764 | 763 | Reserved | Reserved | |||||||
765 | 764 | Reserved | Reserved | |||||||
766 | 765 | Reserved | Reserved | |||||||
767 | 766 | Reserved | Reserved | |||||||
768 | 767 | Reserved | Reserved | |||||||
769 | 768 | Reserved | Reserved | |||||||
770 | 769 | Reserved | Reserved | |||||||
771 | 770 | Reserved | Reserved | |||||||
772 | 771 | Reserved | Reserved | |||||||
773 | 772 | Reserved | Reserved | |||||||
774 | 773 | Reserved | Reserved | |||||||
775 | 774 | HREG_EFFECTIVE_CIRCULATION | uint16 | 1 | Fan speed, circulation air | Circulation air fan's current speed | Kotil<E4>mp<F6>, EMB, Mixbox | |||
776 | 775 | Reserved | Reserved | |||||||
777 | 776 | Reserved | Reserved | |||||||
778 | 777 | Reserved | Reserved | |||||||
779 | 778 | Reserved | Reserved | |||||||
780 | 779 | Reserved | Reserved | |||||||
781 | 780 | HREG_AO1_VOLT | uint16 | 10 | AO1 voltage | The voltage on Analog Output 1 | NB: Only on sw 1.18 and above | |||
782 | 781 | HREG_AO2_VOLT | uint16 | 10 | AO2 voltage | The voltage on Analog Output 2 | NB: Only on sw 1.18 and above | |||
783 | 782 | HREG_AO3_VOLT | uint16 | 10 | AO3 voltage | The voltage on Analog Output 3 | NB: Only on sw 1.18 and above | |||
784 | 783 | HREG_AO4_VOLT | uint16 | 10 | AO4 voltage | The voltage on Analog Output 4 | NB: Only on sw 1.18 and above | |||
785 | 784 | HREG_AO5_VOLT | uint16 | 10 | AO5 voltage | The voltage on Analog Output 5 | NB: Only on sw 1.18 and above | |||
786 | 785 | HREG_AO6_VOLT | uint16 | 10 | AO6 voltage | The voltage on Analog Output 6 | NB: Only on sw 1.18 and above | |||
787 | 786 | HREG_AO7_VOLT | uint16 | 10 | AO7 voltage | The voltage on Analog Output 7 | NB: Only on sw 1.18 and above | |||
788 | 787 | HREG_AO8_VOLT | uint16 | 10 | AO8 voltage | The voltage on Analog Output 8 | NB: Only on sw 1.18 and above | |||
789 | 788 | HREG_DI9_PULSE_CNT | uint16 | 1 | DI9 pulse count | Number of pulses detected on DI9 | NB: Only on sw 1.18 and above | |||
790 | 789 | HREG_DI_BITMAP | uint16 | 1 | DI1-12 and X9-GPIO1-3 status | Status bitmap of digital inputs DI1 to DI12 and GPIO pins 1-3 on connector X9 | NB: Only on sw 1.18 and above | |||
791 | 790 | HREG_AI9_VOLT | uint16 | 10 | AI9 voltage | The measured voltage on Analog Input 9 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
792 | 791 | HREG_AI10_VOLT | uint16 | 10 | AI10 voltage | The measured voltage on Analog Input 10 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
793 | 792 | HREG_AI11_VOLT | uint16 | 10 | AI11 voltage | The measured voltage on Analog Input 11 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
794 | 793 | HREG_AI12_VOLT | uint16 | 10 | AI12 voltage | The measured voltage on Analog Input 12 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
795 | 794 | HREG_AI13_VOLT | uint16 | 10 | AI13 voltage | The measured voltage on Analog Input 13 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
796 | 795 | HREG_AI14_VOLT | uint16 | 10 | AI14 voltage | The measured voltage on Analog Input 14 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
797 | 796 | HREG_AI15_VOLT | uint16 | 10 | AI15 voltage | The measured voltage on Analog Input 15 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
798 | 797 | HREG_AI16_VOLT | uint16 | 10 | AI16 voltage | The measured voltage on Analog Input 16 | Input also known as X10_1. NB: long time constant! NB: Only on sw 1.18 and above | |||
799 | 798 | HREG_DO_BITMAP | uint16 | 1 | DO1-8 status | Status bitmap of digital outputs (relays) | NB: Only on sw 1.18 and above | |||
800 | 799 | Reserved | uint16 | 1 | Ping register | Reserved | This register is used by eAir web UI to test if the connection is live |